9 Technical data

105

2013-04-01

Direct current

NiCr-Ni "K" DIN EN 60584

-200 to +1372 °C

0.4 %

100 ppm/K

NiCrSi-NiSi "N" DIN EN 60584

-100 to +1300 °C

0.4 %

100 ppm/K

Pt10Rh-Pt "S" DIN EN 60584

0 to +1768 °C

0.4 %

100 ppm/K

Pt13Rh-Pt "R" DIN EN 60584

0 to +1768 °C

0.4 %

100 ppm/K

Pt30Rh-Pt6Rh "B" DIN EN 60584 300 to 1820 °C

0.4 %

100 ppm/K

W3Re-W25Re "D"

0 to 2495 °C

0.4 %

100 ppm/K

Cold junction

Pt100 internal

Cold junction accuracy

±1 K

Sampling rate

210 ms

Fault tolerance time

5 s time taken into account for all diagnostic tests

Input filter

Digital filter, 2nd order; filter constant can be set from 0 to 100 s

1.The accuracy values refer to the maximum measuring range.

Measuring range

Accuracy

Ambient temperature

influence

4 to 20 mA, voltage drop < 2 V

0.2 %

150 ppm/K

Scaling

Can be freely programmed within the limits

Sampling rate

210 ms

Fault tolerance time

5 s time taken into account for all diagnostic tests

Input filter

Digital filter, 2nd order; filter constant can be set from 0 to 100 s

Special features

Individual probe 4 to 20 mA