13 What to do, if ...

2013-04-01

130

... alarm relay output
is not closed between
terminals 14 and 15 al-
though the OK LED is lit
green (in valid range).

-

The integrated fuse cut-out is

defective,

caused by an excessive relay current.

h

Measure terminal 5 and 7 of the relay when
the LED K1 is lit green using a continuity
test device.

h

The device must be returned to JUMO for
repair.

v

Chapter 2.4 "Service addresses"

... the display is dark,
only the LEDs are lit

-

Display shut-down after time-out was acti-
vated.

h

Press any key

or switch off time-out.

v

Chapter 8.6.8 "Time-out operation"

Description

Cause

Remedy