7 ATEX

2013-04-01

74

electrical circuits cannot have an effect on the intrinsically safe electrical circuits.
Brackets are used for the identification marking of the associated apparatus: e.g. II (1) G [Ex ia] II C.
Associated electrical apparatus can be used in potentially explosive areas if appropriate protection is provided (ignition protec-
tion according to EN 60079-0). If there is insufficient protection, the apparatus must be used outside of the potentially explo-
sive area.
Example:
The JUMO safety

M STB/STW Ex is not in a potentially explosive area, but it is connected to a thermocouple that is in a poten-

tially explosive area. Only the input electrical circuit of the JUMO safety

M STB/STW Ex is intrinsically safe.

The screw terminals that are marked blue and the connected lines are protected with a cover cap.

Figure 6: Cover cap

v

Chapter 4.2 "Removing the cover cap"