6 safety manual – JUMO 14597 safetyM STB/STW Ex - Safety Temperature Limiter and Safety Temperature Monitor Operating Manual User Manual
Page 52
6 Safety Manual
46
Table 9:
Safety feature
Requirement / comment
SIL
The sensor system is included in the
SIL
evaluation
SIL2
SIL3
Operating mode concerning
safety function
Operating mode with lower and higher demand rate possible on a customer-specific
basis
Safety-critical inputs
Temperature sensor inputs 4 to 20 mA current loop
Safety-relevant inputs
Setup and parameterization
Safety-critical output
Alarm contact limit value
Subsystem type
Type B
Safety architecture (JUMO safetyM
STB/STW Ex logic unit)
1oo2D
Safety architecture (sensor system)
SIL2
1oo1
SIL3
1oo2
Hardware fault tolerance (JUMO
safety
M STB/STW Ex logic unit)
HFT=1
Hardware fault tolerance (sensor sys-
tem)
SIL2: HFT=0
SIL3: HFT=1
Safe failure fraction
SIL2 sensor system HFT=0: 90 % to < 99 % SIL3 sensor system HFT=1:
90 % to < 99 %
CCF
Calculation according to DIN EN 61508 Part 7 Appendix D or DIN EN ISO 13849-1
Table F.1 min. 65 %