6 safety manual – JUMO 14597 safetyM STB/STW Ex - Safety Temperature Limiter and Safety Temperature Monitor Operating Manual User Manual

Page 52

Advertising
background image

6 Safety Manual

2013-04-01

46

Table 9:

Safety feature

Requirement / comment

SIL
The sensor system is included in the
SIL
evaluation

SIL2

SIL3

Operating mode concerning
safety function

Operating mode with lower and higher demand rate possible on a customer-specific
basis

Safety-critical inputs

Temperature sensor inputs 4 to 20 mA current loop

Safety-relevant inputs

Setup and parameterization

Safety-critical output

Alarm contact limit value

Subsystem type

Type B

Safety architecture (JUMO safetyM
STB/STW Ex logic unit)

1oo2D

Safety architecture (sensor system)

SIL2
1oo1

SIL3
1oo2

Hardware fault tolerance (JUMO
safety

M STB/STW Ex logic unit)

HFT=1

Hardware fault tolerance (sensor sys-
tem)

SIL2: HFT=0

SIL3: HFT=1

Safe failure fraction

SIL2 sensor system HFT=0: 90 % to < 99 % SIL3 sensor system HFT=1:

90 % to < 99 %

CCF

Calculation according to DIN EN 61508 Part 7 Appendix D or DIN EN ISO 13849-1
Table F.1 min. 65 %

Advertising