4 Electrical connection
20
4 to 20 mA
V
4 to 20 mA for both analog inputs
Caution:
When only one probe (SIL2) is connected, the temperature limiter device is reduced from
SIL3 to SIL2! However,
the internal 2-channel structure (1oo2D) in the device still remains.
Both channels measure the same current signal due to the simplified external wiring.
4
Binary input
Connection to a potential-free contact
5
Analog output:
0 to 20 mA
4 to 20 mA (factory set)
0(2) to 10 V
V
Caution
The analog output is
not part of the safety func-
tion!
9
Voltage supply
Acc. to nameplate
AC:
L1 line conductor
N neutral conductor
DC:
(L+)
(L-)
Legend Comment
Screw terminals
Screw terminals
2
3
+
–
I
x
7
8
+
–
I
x
2
+
–
I
x
7
Ground
4
5
9
10
+
–
I
x,
U
x
L1
N
L1
N
L+ L-
L+ L-