9 offset 2, 10 resistivity 2, 11 filter time 2 – JUMO 14597 safetyM STB/STW Ex - Safety Temperature Limiter and Safety Temperature Monitor Operating Manual User Manual

Page 97: 12 scaling start 2, 13 scaling end 2, Offset 2, Resistivity 2, Filter time 2, Scaling start 2, Scaling end 2

Advertising
background image

8 Configuration level

91

2013-04-01

Parameter

Comment

Value range
(factory setting in

bold)

8.2.9 Offset 2

Using Offset2, a measured value at the analog input
can be corrected by the value entered over the entire
measuring range.

-999.9 to

0.0 to +999.9

8.2.10 Resistivity 2

Analog-input2 lead wire resistance

in 2-wire circuit
This value is used to compensate the resistance of the
probe line and depends on the line length.
Enter the ohmic resistance of the probe line here to
achieve the best possible temperature measurement.

0.0 to 30.0 ohm

8.2.11 Filter time 2

Time constant of the digital input filter

2nd order for analog input 2
If the input signal changes suddenly, approx. 26 % of
the change is recorded following a period that corre-
sponds to the filter time constant dF (2 × dF: approx.
59 %; 5 × dF: approx. 96 %).
Value 0 means: filter switched off

If the filter time is long:
- Interfering signals are better absorbed
- Measured value display responds more slowly to
changes

0.0 to

0.6 to 100 sec

8.2.12 Scaling start 2

Important information: This setting only occurs if the
sensor type 2 was set to 4 to 20 mA.

Here, the user must select which value (e.g. pressure)
should be displayed at 4 mA.

-9999 to

0 to +9999

8.2.13 Scaling end 2

Here, the user must select which value (e.g. pressure)
should be displayed at 20 mA.

-9999 to

100 to +9999