10 Setup program

121

2013-04-01

3

h

In the Analog input menu, set

Single 4 to 20 mA. Further

input fields for scaling appear.

h

For both channels, enter

Start: 0 and End: 500 and con-

firm with OK.

4

h

In the Limiter/Monitor menu, set

STB or Initial STB com-

missioning. Set Switching behavior: to Min. alarm and
confirm with OK.

h

Enter the required

limit value (in Pa) and hysteresis.

Step

Action

Description