12 Error messages

127

2013-04-01

Diagnosis function

FLASH defective

1

Internal

An error was detected during the cyclic memory test of the ROM.

RAM defective

1

Internal

An error was detected during the cyclic memory test of the RAM.

CRC config.

1

Internal

An error was detected by the checksum test (CRC16) in the configuration of
the diagnosis function.

CRC calib.

1

Internal

An error was detected by the checksum test (CRC16) in the calibration data
of the diagnosis function.

Configuration

Internal

The configuration contains invalid data.

SW version

1

Internal

The software versions are not valid.

Editing

Internal

An error has occurred during editing.

V too low

Internal

The internal voltage supply value has fallen below the permitted range.

V too high

Internal

The permitted range of the internal voltage supply has been exceeded.

Int. communic.

1

Internal

An error has occurred during internal communication.

Difference

Plant

The difference (channel 1 minus channel 2) of the measured values has ex-
ceeded the maximum permitted value.

Switching operations

Internal

The configured limit of switching cycles has been exceeded.

(There is only one counter as all alarm relays always switch.)

The error can be acknowledged once the current counter is reduced or the
limit is increased.

(So that the switching operations are not accidentally set to 0 in the event of
further errors)

USB communic.

Internal

An error has occurred during USB communication.

Error display (Err)

Origin

Cause/remedy