6 safety manual, Figure 1, Table 7: low demand table pfd – JUMO 14597 safetyM STB/STW Ex - Safety Temperature Limiter and Safety Temperature Monitor Operating Manual User Manual

Page 49

Advertising
background image

6 Safety Manual

43

2013-04-01

The sensor, logic unit, and actuator together form a safety-related system that performs a safety function. The "average proba-
bility of dangerous failures of the entire safety-related system" (PFD

avg

) is usually divided up into the sensor, logic unit, and ac-

tuator subsystems according to the following diagram.

Figure 1:

Typical subdivision of the "average probability of dangerous failures of a safety function on demand" (PFD

avg

) into subsystems

The specifications related to functional safety in this Safety Manual include sensor systems (resistance temperature probes,
thermocouples), logic unit (701155), and (as signal contact) the relay output in the JUMO safetyM STB/STW Ex system.

The actuator (for example a power contactor) is plant-related and must be taken into consideration separately according to the
standard for the safety loop.

Table 7: Low demand table PFD

Safety Integrity Level

(SIL)

Operating mode with low demand rate

PFD

avg

(low demand mode)

4

10

-5

to < 10

-4

3

10

-4

to < 10

-3

2

10

-3

to < 10

-2

1

10

-2

to < 10

-1