6 safety manual, Table 1: achievable sil – JUMO 14597 safetyM STB/STW Ex - Safety Temperature Limiter and Safety Temperature Monitor Operating Manual User Manual

Page 40

Advertising
background image

6 Safety Manual

2013-04-01

34

Important information:

Variants 1 to 4 were evaluated with JUMO probes according to data sheets 901006 and 902006. For variant 5 no sensor sys-
tem was included (only the JUMO safety

M STB/STW Ex). In this case, the plant operator selects the sensor system. For this

reason, the plant operator is responsible for evaluating the achievable SIL.

If the used SIL-capable sensor consists of hardware and software (e.g. transmitter), the maximum SIL that can be achieved –
irrespective of the architecture – is the one according to which the sensor software was developed (so, for example, if the sen-
sor software has SIL2, the max. achievable SIL is 2).

The possibility of connecting passive sensors such as dual thermocouples or Pt100/1000 sensors means that the sensors do
not necessarily require an SIL qualification. In this case, the specification of the failure rates for the passive sensors is sufficient

Table 1: Achievable SIL

Variant

Connected sensors

Sensor system
architecture

Logic ar-
chitecture

Achievable SIL

1

1x Pt100 2-wire circuit

1oo1

1oo2D

SIL2

1a

2x Pt100/1000 2-wire circuit

1oo2

1oo2D

SIL3

2

2x Pt100/1000 3-wire circuit

1oo2

1oo2D

SIL3

3

2x thermocouple

1oo2

1oo2D

SIL3

4

1x Pt100/1000 2-wire + 3-
wire circuit
1x thermocouple

1oo2

1oo2D

SIL3

5

STB/STW 701155 without
sensor system 1oo2D archi-
tecture
No probe or use of 4 to
20 mA
This means the sensor is not
taken into account in the cal-
culation.

Sensors con-
nected by the
plant operator;
architecture
acc. to connec-
tion 1oo1 or
1oo2

1oo2D

SIL of the used
sensor (HW only)

Max. achievable SIL of the
system with 1oo1 sensor
system architecture

Max. achievable SIL of the
system with 1oo2 sensor
system architecture

SIL1

SIL1

SIL2

SIL2

SIL2

SIL3

SIL3

SIL3

SIL3