Table 2 — physical data — unit 589a – Bryant 589A User Manual

Page 15

Advertising
background image

Table 2 — Physical Data — Unit 589A

UNIT SIZE 589A

024040

024060

030040

030060

030080

036060

036080

036100

036120

NOMINAL CAPACITY (ton)

2

2

2

1

2

2

1

2

2

1

2

3

3

3

3

OPERATING WEIGHT (lb)

Without Base Rail

333

345

336

348

348

366

366

378

378

With Optional Base Rail

357

369

360

372

372

390

390

402

402

COMPRESSORS

Scroll

Quantity

1

REFRIGERANT (R-22)

Charge (lb)

3.9

3.9

4.5

4.5

4.5

5.4

5.4

5.4

5.4

REFRIGERANT METERING DEVICE

Acutrol™ Device

Orifice ID (in.)

.034

.034

.030

.030

.030

.032

.032

.032

.032

CONDENSER COIL

Rows...Fins/in.

2...17

2...17

2...17

2...17

2...17

2...17

2...17

2...17

2...17

Face Area (sq ft)

7.0

7.0

7.0

7.0

7.0

7.0

7.0

7.0

7.0

CONDENSER FAN

Nominal Cfm

2200

2200

2200

2200

2200

2200

2200

2200

2200

Diameter (in.)

20

20

20

20

20

20

20

20

20

Motor Hp (Rpm)

1

4

(1100)

1

4

(1100)

1

4

(1100)

1

4

(1100)

1

4

(1100)

1

4

(1100)

1

4

(1100)

1

4

(1100)

1

4

(1100)

EVAPORATOR COIL

Rows Fins/in.

2...15

2...15

3...15

3...15

3...15

4...15

4...15

4...15

4...15

Face Area (sq ft)

3.6

3.6

2.7

2.7

2.7

3.6

3.6

3.6

3.6

EVAPORATOR FAN*

Direct Drive

Nominal Airflow (Cfm)

800

800

1000

1000

1000

1200

1200

1200

1200

Size (in.)

10 x 10

10 x 10

10 x 10

10 x 10

10 x 10

10 x 10

10 x 10

10 x 10

10 x 10

Motor Hp

1

4

1

4

1

4

1

4

1

4

1

2

1

2

1

2

1

2

FURNACE SECTION†

Burner Orifice (Qty...drill size)

Natural Gas

1...32

2...41

1...32

2...40

2...32

2...40

2...32

2...30

3...32

Burner Orifice (Qty...drill size)

Propane Gas

1...41

2...47

1...41

2...47

2...42

2...47

2...42

2...40

3...42

RETURN-AIR FILTERS (in.)**

Disposable

24 x 24

24 x 24

24 x 24

24 x 24

24 x 24

24 x 24

24 x 24

24 x 24

24 x 24

UNIT SIZE 589A

042060

042080

042100

042120

048080

048100

048120

048140

060080

060100

060120

060140

NOMINAL CAPACITY (ton)

3

1

2

3

1

2

3

1

2

3

1

2

4

4

4

4

5

5

5

5

OPERATING WEIGHT (lb)

Without Base Rail

391

391

403

403

422

434

434

434

453

465

465

465

With Optional Base Rail

415

415

427

427

446

458

458

458

477

489

489

489

COMPRESSORS

Scroll

Quantity

1

REFRIGERANT (R-22)

Charge (lb)

5.7

5.7

5.7

5.7

5.8

5.8

5.8

5.8

7.00

7.00

7.00

7.00

REFRIGERANT METERING

Acutrol Device

DEVICE

Orifice ID (in.)

.034

.034

.034

.034

.034

.034

.034

.034

.030

.030

.030

.030

CONDENSER COIL

Rows...Fins/in.

2...17

2...17

2...17

2...17

2...17

2...17

2...17

2...17

2...17

2...17

2...17

2...17

Face Area (sq ft)

8.7

8.7

8.7

8.7

8.7

8.7

8.7

8.7

8.67

8.67

8.67

8.67

CONDENSER FAN

Nominal Cfm

2400

2400

2400

2400

2400

2400

2400

2400

2400

2400

2400

2400

Diameter (in.)

20

20

20

20

20

20

20

20

20

20

20

20

Motor Hp (Rpm)

1

4

(1100)

1

4

(1100)

1

4

(1100)

1

4

(1100)

1

4

(1100)

1

4

(1100)

1

4

(1100)

1

4

(1100)

1

3

(1050)

1

3

(1050)

1

3

(1050)

1

3

(1050)

EVAPORATOR COIL

Rows Fins/in.

3...15

3...15

3...15

3...15

4...15

4...15

4...15

4...15

4...15

4...15

4...15

4...15

Face Area (sq ft)

4.4

4.4

4.4

4.4

4.4

4.4

4.4

4.4

4.44

4.44

4.44

4.44

EVAPORATOR FAN*

Direct Drive

Nominal Airflow (Cfm)

1400

1400

1400

1400

1600

1600

1600

1600

1995

1995

1995

1995

Size (in.)

10 x 10

10 x 10

10 x 10

10 x 10

10 x 10

10 x 10

10 x 10

10 x 10

10 x 11

10 x 11

10 x 11

10 x 11

Motor Hp

3

4

3

4

3

4

3

4

3

4

3

4

3

4

3

4

1

1

1

1

FURNACE SECTION†

Burner Orifice (Qty...drill size)

Natural Gas

2...40

2...32

2...30

3...32

2...32

2...30

3...32

3...31

2...32

2...30

3...32

3...31

Burner Orifice (Qty...drill size)

Propane Gas

2...47

2...42

2...40

3...42

2...42

2...40

3...42

3...40

3...42

2...40

3...42

3...40

RETURN-AIR FILTERS (in.)**

Disposable

24 x 30

24 x 30

24 x 30

24 x 30

24 x 30

24 x 30

24 x 30

24 x 30

24 x 30

24 x 30

24 x 30

24 x 30

*

Size 048 evaporator fan is equipped with a 460-v or integrated control motor (ICM). Size 060 evaporator fan is
equipped with an ICM only. The ICM provides variable speed.

†Based on an altitude of 0-2000 feet.

**Required filter sizes shown are based on the ARI (Air Conditioning & Refrigeration Institute) rated heating airflow

at a velocity of 300 ft/min for throwaway type or 450 ft/min for high-capacity type. For non-standard air filters, air
filter pressure drop must not exceed 0.08 in. wg.

—15—