Table 3 — Maximum Gas Flow Capacity*

NOMINAL

IRON PIPE,

SIZE

(in.)

INTERNAL

DIAMETER

(in.)

LENGTH OF PIPE, FT†

10

20

30

40

50

60

70

80

90

100

125

150

175

200

1

2

.622

175

120

97

82

73

66

61

57

53

50

44

40

3

4

.824

360

250

200

170

151

138

125

118

110

103

93

84

77

72

1

1.049

680

465

375

320

285

260

240

220

205

195

175

160

145

135

1

1

4

1.380

1400

950

770

600

580

530

490

460

430

400

360

325

300

280

1

1

2

1.610

2100

1460

1180

990

900

810

750

690

650

620

550

500

460

430

*Capacity of pipe in cu ft of gas per hr for gas pressure of 0.5 psig or less. Pressure drop of 0.5-in. wg (based on

a 0.60 specific gravity gas). Refer to Table C-4, National Fire Protection Association NFPA 54.

†This length includes an ordinary number of fittings.

SUPPLY DUCT OPENING

RETURN DUCT OPENING

Fig. 16 — Supply and Return Duct Openings

Fig. 17 — Lance Location for Vertical Duct

Opening Cover

Fig. 18 — Vertical Duct Cover Removed

Fig. 19 — Removal of Vertical Discharge

Opening Cover