REQ’D CLEARANCES FOR SERVICING. in. (mm)

Duct panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)
Side opposite ducts

. . . . . . . . . . . . . . . . . . . . . 36 (914)

Compressor access

. . . . . . . . . . . . . . . . . . . . . 36 (914)

(Except for NEC requirements)

REQ’D CLEARANCES TO COMBUSTIBLE MAT’L. in. (mm)

Maximum extension of overhangs . . . . . . . . . . . . . . . 48 (1219)
Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 (356)
Duct side of unit . . . . . . . . . . . . . . . . . . . . . . . . 2 (51)
Side opposite ducts

. . . . . . . . . . . . . . . . . . . . . 14 (356)

Bottom of unit . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Flue panel

. . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)

NEC REQ’D CLEARANCES. in. (mm)

Between units, control box side . . . . . . . . . . . . . . . . 42 (1067)
Unit and ungrounded surfaces, control box side . . . . . . . . . 36 (914)
Unit and block or concrete walls and other grounded
surfaces, control box side . . . . . . . . . . . . . . . . . . 42 (1067)

UNIT
588A

ELECTRICAL

CHARACTERISTICS

UNIT WEIGHT

CORNER WEIGHT

(lb/kg)

UNIT HEIGHT

(in./mm)

lb

kg

A

B

C

D

E

018040

208/230-1-60

272

123

81/37

62/28

76/35

53/24

24.1/613

024040

208/230-1-60

303

138

97/44

43/20

123/56

40/18

24.1/613

024060

208/230-1-60

315

143

100/45

46/21

126/57

43/20

24.1/613

030040

208/230-1-60, 208/230-3-60

320

145

100/45

47/21

126/57

47/21

24.1/613

030060/080

208/230-1-60, 208/230-3-60

332

149

103/46

50/22

129/58

50/23

24.1/613

036060/080

208/230-1-60, 208/230-3-60, 460-3-60

336

153

86/39

76/35

111/50

63/29

24.1/613

036100/120

208/230-1-60, 208/230-3-60, 460-3-60

348

158

89/40

79/36

114/52

66/30

24.1/613

042060/080

208/230-1-60, 208/230-3-60, 460-3-60

375

170

95/43

86/39

119/54

75/34

28.1/714

042100/120

208/230-1-60, 208/230-3-60, 460-3-60

387

176

98/45

89/40

122/55

78/35

28.1/714

UNIT
588A

F

in./mm

G

in./mm

CENTER OF GRAVITY in./mm

X

Y

Z

018040

16

9

16

/420.7

18

15

16

/481.0

25.07/637

20.59/523

10.85/276

024040

27.07/688

23.35/593

024060

26.98/685

23.27/591

030040

26.71/678

23.46/596

030060/080

27.15/689

22.36/568

036060/080

27.50/698

22.48/571

036100/120

27.40/696

22.44/570

042060/080

20

9

16

/522.3

22

15

16

/582.6

27.01/686

22.44/570

12.7/321

042100/120

26.94/684

22.44/570

LEGEND

CG

Center of Gravity

COND — Condenser
LV

Low Voltage

MAT’L

Material

NEC

National Electrical Code

REQ’D — Required

NOTES:
1. Clearances must be maintained to prevent recirculation of air from outdoor-

fan discharge.

2. Adequate clearance around air openings into combustion chamber must

be provided.

Fig. 2 — 588A018-042 Without Base Rail, Unit Dimensions

—2—