Bryant 589A User Manual

Page 3

Advertising
background image

REQ’D CLEARANCES FOR SERVICING. in. (mm)

Duct panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)
Side opposite ducts

. . . . . . . . . . . . . . . . . . . . . 36 (914)

Compressor access

. . . . . . . . . . . . . . . . . . . . . 36 (914)

(Except for NEC requirements)

REQ’D CLEARANCES TO COMBUSTIBLE MAT’L. in. (mm)

Maximum extension of overhangs . . . . . . . . . . . . . . . 48 (1219)
Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 (356)
Duct side of unit . . . . . . . . . . . . . . . . . . . . . . . . 2 (51)
Side opposite ducts

. . . . . . . . . . . . . . . . . . . . . 14 (356)

Bottom of unit . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Flue panel

. . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)

NEC REQ’D CLEARANCES. in. (mm)

Between units, control box side . . . . . . . . . . . . . . . . 42 (1067)
Unit and ungrounded surfaces, control box side . . . . . . . . . 36 (914)
Unit and block or concrete walls and other grounded
surfaces, control box side . . . . . . . . . . . . . . . . . . 42 (1067)

UNIT
588A

ELECTRICAL

CHARACTERISTICS

UNIT WEIGHT

CORNER WEIGHT

(lb/kg)

UNIT HEIGHT

(in./mm)

lb

kg

A

B

C

D

E

018040

208/230-1-60

296

135

87/40

68/31

82/37

59/27

27.4/697

024040

208/230-1-60

327

149

103/47

49/22

129/59

46/21

27.4/697

024060

208/230-1-60

339

155

106/48

52/24

132/60

49/22

27.4/697

030040

208/230-1-60, 208/230-3-60

344

157

106/48

53/24

132/60

53/24

27.4/697

030060/080

208/230-1-60, 208/230-3-60

356

162

102/46

71/32

123/56

60/27

27.4/697

036060/080

208/230-1-60, 208/230-3-60, 460-3-60

360

164

92/42

82/37

117/53

69/31

27.4/697

036100/120

208/230-1-60, 208/230-3-60, 460-3-60

372

169

95/43

85/39

120/55

72/33

27.4/697

042060/080

208/230-1-60, 208/230-3-60, 460-3-60

399

181

101/46

92/42

125/57

81/37

31.4/798

042100/120

208/230-1-60, 208/230-3-60, 460-3-60

411

187

104/47

95/43

128/58

84/38

31.4/798

UNIT
588A

F

in./mm

G

in./mm

CENTER OF GRAVITY in./mm

X

Y

Z

018040

19

7

8

/504.8

22

1

4

/565.4

25.04/636

22.72/577

13.16/334.3

024040

26.90/683.3

20.17/512.3

024060

26.82/681.2

20.22/513.6

030040

26.57/674.9

20.1 /509.3

030060/080

26.93/684

21.1 /535.4

036060/080

27.31/693.7

21.0 /532.6

036100/120

27.23/691.6

21.0 /533.1

042060/080

23

7

8

/606.4

26

1

4

/666.8

26.87/682.5

21.0 /533.1

14.96/380

042100/120

26.81/681

21.0 /533.7

LEGEND

CG

Center of Gravity

COND — Condenser
LV

Low Voltage

MAT’L

Material

NEC

National Electrical Code

REQ’D — Required

NOTES:
1. Clearances must be maintained to prevent recirculation of air from outdoor-

fan discharge.

2. Adequate clearance around air openings into combustion chamber must

be provided.

Fig. 3 — 588A018-042 With Optional Base Rail, Unit Dimensions

—3—

Advertising