Table 9D — Superheat Charging Table, 589A042

TEMP (F)

OUTDOOR
ENTERING

AIR

INDOOR AIR — CFM

1400

Indoor Air — Ewb (F)

54

56

58

60

62

64

66

68

70

72

74

76

65

SPH

23.9

23.9

23.9

23.9

24.4

24.9

25.5

25.8

26.1

26.5

25.6

24.7

70

SPH

21.9

21.9

21.9

21.9

22.4

22.9

23.4

23.7

24.1

24.5

24.0

23.5

75

SPH

19.8

19.8

19.8

19.8

20.3

20.8

21.3

21.7

22.0

22.4

22.4

22.4

80

SPH

16.3

16.3

16.3

16.3

17.9

19.6

21.3

21.5

21.7

21.8

21.8

21.8

85

SPH

12.7

12.7

12.7

12.7

15.6

18.4

21.3

21.3

21.3

21.3

21.3

21.3

90

SPH

9.2

9.2

9.2

9.2

12.0

14.9

17.8

18.7

19.7

20.8

20.8

20.8

95

SPH

5.6

5.6

5.6

5.6

8.5

11.3

14.2

16.2

18.2

20.2

20.2

20.2

100

SPH

*

*

*

*

*

8.0

10.6

13.1

15.6

18.1

18.9

19.6

105

SPH

*

*

*

*

*

*

7.1

10.1

13.1

16.1

17.6

19.1

110

SPH

*

*

*

*

*

*

*

7.0

10.5

14.0

15.5

17.0

115

SPH

*

*

*

*

*

*

*

*

8.0

12.0

13.5

15.0

LEGEND

Ewb — Entering Wet Bulb
SPH — Superheat at Compressor (F)

*Do not attempt to charge system under these conditions — refrigerant

slugging may occur.

Table 9E — Superheat Charging Table, 589A048

TEMP (F)

OUTDOOR
ENTERING

AIR

INDOOR AIR — CFM

1600

Indoor Air — Ewb (F)

54

56

58

60

62

64

66

68

70

72

74

76

65

SPH

27.2

27.2

27.2

27.2

27.0

26.7

26.5

26.0

25.6

25.1

24.5

24.0

70

SPH

25.0

25.0

25.0

25.0

24.8

24.6

24.5

24.5

24.5

24.6

23.8

23.1

75

SPH

22.8

22.8

22.8

22.8

22.7

22.5

22.4

22.9

23.5

24.0

23.1

22.2

80

SPH

20.6

20.6

20.6

20.6

20.5

20.4

20.3

21.4

22.4

23.5

22.4

21.4

85

SPH

18.3

18.3

18.3

18.3

18.3

18.3

18.3

19.8

21.4

22.9

21.8

20.6

90

SPH

13.3

13.3

13.3

13.3

14.2

15.2

16.3

17.8

19.3

20.9

20.4

19.9

95

SPH

8.2

8.2

8.2

8.2

10.2

12.2

14.2

15.7

17.3

18.8

19.0

19.2

100

SPH

*

*

*

*

6.3

8.4

10.6

12.9

15.2

17.5

18.1

18.7

105

SPH

*

*

*

*

*

*

7.1

10.1

13.1

16.1

17.1

18.2

110

SPH

*

*

*

*

*

*

*

7.1

10.5

14.0

15.3

16.6

115

SPH

*

*

*

*

*

*

*

*

8.0

12.0

13.5

15.0

LEGEND

Ewb — Entering Wet Bulb
SPH — Superheat at Compressor (F)

*Do not attempt to charge system under these conditions — refrigerant

slugging may occur.

Table 9F — Superheat Charging Table, 589A060

TEMP (F)

OUTDOOR
ENTERING

AIR

INDOOR AIR — CFM

1995

Indoor Air — Ewb (F)

54

56

58

60

62

64

66

68

70

72

74

76

65

SPH

20.1

20.1

20.1

20.1

20.1

20.1

22.6

25.2

25.6

26.1

26.6

27.0

70

SPH

16.5

16.5

16.5

16.5

17.3

18.0

20.6

23.1

24.0

24.8

25.6

26.5

75

SPH

13.0

13.0

13.0

13.0

14.5

16.0

18.5

21.1

22.3

23.5

24.7

25.9

80

SPH

10.9

10.9

10.9

10.9

12.4

13.9

16.5

19.0

20.6

22.2

23.8

25.4

85

SPH

8.9

8.9

8.9

8.9

10.4

11.9

14.4

17.0

18.9

20.9

22.9

24.9

90

SPH

6.9

6.9

6.9

6.9

8.4

9.9

12.4

14.9

17.3

19.6

22.0

24.3

95

SPH

5.0

5.0

5.0

5.0

6.3

7.8

10.3

12.9

15.6

18.3

21.1

23.8

100

SPH

*

*

*

*

*

5.8

8.3

10.8

13.9

17.0

20.1

23.2

105

SPH

*

*

*

*

*

*

6.2

8.8

12.3

15.7

19.2

22.7

110

SPH

*

*

*

*

*

*

*

6.7

10.6

14.4

18.3

22.2

115

SPH

*

*

*

*

*

*

*

*

8.9

13.1

17.4

21.6

LEGEND

Ewb — Entering Wet Bulb
SPH — Superheat at Compressor (F)

*Do not attempt to charge system under these conditions — refrigerant

slugging may occur.

—40—

Advertising