REQ’D CLEARANCES FOR SERVICING. in. (mm)

Duct panel . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Unit top . . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)
Side opposite ducts . . . . . . . . . . . . . . . . . . . . 36 (914)
Compressor access . . . . . . . . . . . . . . . . . . . . 36 (914)
(Except for NEC requirements)

REQ’D CLEARANCES TO COMBUSTIBLE MAT’L. in. (mm)

Maximum extension of overhangs . . . . . . . . . . . . . 48 (1219)
Unit top . . . . . . . . . . . . . . . . . . . . . . . . . 14 (356)
Duct side of unit

. . . . . . . . . . . . . . . . . . . . . . 2 (51)

Side opposite ducts . . . . . . . . . . . . . . . . . . . . 14 (356)
Bottom of unit

. . . . . . . . . . . . . . . . . . . . . . . . . 0

Flue panel . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)

NEC REQ’D CLEARANCES. in. (mm)

Between units, control box side . . . . . . . . . . . . . . 42 (1067)
Unit and ungrounded surfaces, control box side

. . . . . . . 36 (914)

Unit and block or concrete walls and other grounded
surfaces, control box side

. . . . . . . . . . . . . . . . 42 (1067)

UNIT
589A

ELECTRICAL

CHARACTERISTICS

UNIT WEIGHT

CORNER WEIGHT

(lb/kg)

lb

kg

A

B

C

D

024040

208/230-1-60

357

163

110/50

56/25

136/62

55/25

024060

208/230-1-60

369

168

113/51

59/27

139/63

58/26

030040

208/230-1-60

360

164

103/47

72/33

124/56

61/28

030060/080

208/230-1-60

372

169

106/48

75/34

127/58

64/29

036060/080

208/230-1-60, 208/230-3-60, 460-3-60

390

177

100/45

90/41

123/56

77/35

036100/120

208/230-1-60, 208/230-3-60, 460-3-60

402

183

103/47

93/42

127/57

80/36

UNIT
589A

CENTER OF GRAVITY (in./mm)

X

Y

Z

024040

26.57/674.9

20.17/512.3

14.96/380.0

024060

26.51/673.3

20.22/513.6

14.96/380.0

030040

26.90/683.3

21.09/535.7

14.96/380.0

030060/080

26.83/681.5

21.11/536.2

14.96/380.0

036060/080

26.99/685.5

21.14/537.0

14.96/380.0

036100/120

26.92/683.8

21.14/537.0

14.96/380.0

LEGEND

CG

Center of Gravity

COND — Condenser
LV

Low Voltage

MAT’L

Material

NEC

National Electrical Code

REQ’D — Required

NOTES:
1. Clearances must be maintained to prevent recirculation of air from outdoor-

fan discharge.

2. Adequate clearance around air openings into combustion chamber must

be provided.

Fig. 7 — 589A024-036 With Optional Base Rail, Unit Dimensions

—7—