REQ’D CLEARANCES FOR SERVICING. in. (mm)

Duct panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)
Side opposite ducts

. . . . . . . . . . . . . . . . . . . . . 36 (914)

Compressor access

. . . . . . . . . . . . . . . . . . . . . 36 (914)

(Except for NEC requirements)

REQ’D CLEARANCES TO COMBUSTIBLE MAT’L. in. (mm)

Maximum extension of overhangs . . . . . . . . . . . . . . . 48 (1219)
Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 (356)
Duct side of unit . . . . . . . . . . . . . . . . . . . . . . . . 2 (51)
Side opposite ducts

. . . . . . . . . . . . . . . . . . . . . 14 (356)

Bottom of unit . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Flue panel

. . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)

LEGEND

CG

Center of Gravity

COND

Condenser

LV

Low Voltage

MAT’L

Material

NEC

National Electrical Code

REQ’D — Required

UNIT
589A

ELECTRICAL

CHARACTERISTICS

UNIT WEIGHT

CORNER WEIGHT

(lb/kg)

lb

kg

A

B

C

D

042060/080

208/230-1-60, 208/230-3-60, 460-3-60

415

189

106/48

97/44

126/57

86/39

042100/120

208/230-1-60, 208/230-3-60, 460-3-60

427

194

109/50

100/45

129/59

89/40

048080

208/230-1-60, 208/230-3-60, 460-3-60

446

293

115/52

91/41

164/75

76/35

048100/120/140

208/230-1-60, 208/230-3-60, 460-3-60

458

208

118/54

94/43

167/76

79/36

060080

208/230-1-60, 208/230-3-60

477

217

123/56

99/45

173/79

82/37

060100/120/140

208/230-1-60, 208/230-3-60

489

222

126/57

102/46

173/79

88/40

UNIT
589A

CENTER OF GRAVITY (in./mm)

X

Y

Z

042060/080

26.55/674.4

21.22/539.0

17.66/448.6

042100/120

26.50/673.0

21.24/539.6

17.66/448.6

048080

28.25/717.6

20.04/509.0

17.66/448.6

048100/120/140

28.16/715.3

20.08/510.0

17.66/448.6

060080

28.18/715.6

20.19/512.8

17.66/448.6

060100/120/140

27.79/705.9

20.23/513.8

17.66/448.6

NOTES:
1. Clearances must be maintained to prevent recirculation of air from outdoor-

fan discharge.

2. Adequate clearance around air openings into combustion chamber must be

provided.

NEC REQ’D CLEARANCES. in. (mm)

Between units, control box side . . . . . . . . . . . . . . . . 42 (1067)
Unit and ungrounded surfaces, control box side . . . . . . . . . 36 (914)
Unit and block or concrete walls and other grounded
surfaces, control box side . . . . . . . . . . . . . . . . . . 42 (1067)

Fig. 9 — 589A042-060 With Optional Base Rail, Unit Dimensions

—9—