Table 12 — Dry-Coil Air Delivery* — Downflow Discharge at 230 and 460 V — Unit 588A

(Deduct 10% from Cfm and Watts for 208 V Operation)

UNIT
588A

MOTOR

SPEED

AIR

DELIVERY

EXTERNAL STATIC PRESSURE (in. wg)

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

018

Low

Watts

295

251

223

201

176

149

124

Cfm

821

817

753

665

536

343

164

High

Watts

401

376

346

322

294

272

250

229

219

Cfm

1334

1253

1128

996

816

658

461

246

167

024,
030

Low

Watts

285

284

282

278

274

270

261

251

244

230

Cfm

798

761

727

682

634

581

525

450

371

304

Med

Watts

378

371

368

362

357

343

332

315

301

283

Cfm

1011

982

948

906

858

771

703

597

492

387

High

Watts

520

511

487

472

451

431

411

385

362

341

Cfm

1342

1309

1237

1181

1106

1007

892

745

610

471

036

Low

Watts

460

439

423

398

379

349

322

297

270

246

Cfm

1191

1136

1081

1005

907

795

687

579

471

349

Med

Watt

511

492

470

450

420

392

364

332

308

275

Cfm

1316

1244

1178

1104

1005

891

784

657

535

389

High

Watts

655

631

603

584

552

522

492

459

433

398

Cfm

1541

1458

1367

1292

1178

1053

920

806

662

509

042

Low

Watts

637

612

587

560

526

493

455

Cfm

1500

1450

1405

1350

1290

1200

1105

High

Watts

790

750

700

679

639

608

574

547

Cfm

1750

1675

1604

1509

1421

1323

1221

1094

048

Low

Watts

847

784

746

708

646

609

563

516

Cfm

1995

1901

1822

1730

1580

1477

1319

1178

High

Watts

909

852

820

801

751

687

639

Cfm

2018

1896

1814

1729

1582

1380

1270

060

Low

Watts

983

950

923

885

845

804

751

697

665

633

Cfm

1838

1808

1755

1702

1628

1553

1446

1339

1257

1175

Med

Watts

1115

1083

1045

1006

964

921

872

823

783

742

Cfm

2067

2023

1957

1891

1807

1723

1612

1501

1392

1282

High

Watts

1284

1201

1166

1131

1092

1053

1001

950

907

864

Cfm

2167

2108

2038

1968

1882

1796

1676

1555

1437

1318

*Air delivery values are without air filter and are for dry coil. See

Table 17 for wet coil pressure drop. Deduct field-supplied air filter
pressure drop and wet coil pressure drop to obtain external static
pressure available for ducting.

†Unit air delivery is outside of operating range.

NOTE: Do not operate the unit at a cooling airflow that is less than
350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator-
coil icing may occur at airflows below this point. Water blow-off may
occur at airflows above 450 cfm per 12,000 Btuh of rated cooling
capacity.

Table 13 — Dry-Coil Air Delivery* — Horizontal Discharge at 230 and 460 V — Unit 589A

(Deduct 10% from Cfm and Watts for 208 V Operation)

UNIT
589A

MOTOR

SPEED

AIR

DELIVERY

EXTERNAL STATIC PRESSURE (in. wg)

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

024,
030

Low

Watts

280

275

265

255

250

245

240

Cfm

820

810

755

700

660

600

560

Med

Watts

365

360

350

345

340

330

320

310

300

Cfm

1025

1010

975

940

900

850

800

720

630

High

Watts

490

480

470

460

445

430

410

390

380

Cfm

1300

1255

1200

1150

1080

1005

915

790

620

036

Low

Watts

520

495

474

458

445

425

Cfm

1375

1335

1290

1240

1200

1140

Med

Watts

575

560

535

510

480

460

440

425

Cfm

1520

1490

1450

1400

1380

1300

1200

1080

High

Watts

650

614

575

540

510

480

Cfm

1560

1500

1380

1280

1170

1060

042

Low

Watts

490

480

470

460

450

430

410

390

Cfm

1400

1380

1340

1300

1250

1200

1140

1070

Med

Watts

590

580

560

545

525

505

480

450

420

Cfm

1600

1560

1540

1470

1430

1360

1300

1220

1120

High

Watts

700

670

640

600

560

500

Cfm

1780

1670

1600

1480

1340

1100

048**

Low

Watts

1050

1000

970

930

870

810

750

680

600

Cfm

1850

1830

1800

1785

1750

1700

1640

1500

1330

High

Watts

1050

1000

930

870

810

740

665

Cfm

2000

1940

1850

1750

1635

1500

1300

*Air delivery values are without air filter and are for dry coil. See

Table 17 for wet coil pressure drop. Deduct field-supplied air filter
pressure drop and wet coil pressure drop to obtain external static
pressure available for ducting.

†Unit air delivery is outside of operating range.

**For 460 v units only.

NOTE: Do not operate the unit at a cooling airflow that is less than
350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator-
coil icing may occur at airflows below this point. Water blow-off may
occur at airflows above 450 cfm per 12,000 Btuh of rated cooling
capacity.