Table 8C — Superheat Charging Table, 588A030

TEMP (F)

OUTDOOR
ENTERING

AIR

INDOOR AIR — CFM

1000

Indoor Air — Ewb (F)

54

56

58

60

62

64

66

68

70

72

74

76

65

SPH

14.2

15.1

16.1

17.1

19.2

21.3

23.3

24.7

25.9

27.2

27.8

28.5

70

SPH

13.6

14.1

14.6

15.0

17.1

19.2

21.3

22.8

24.2

25.7

26.3

26.9

75

SPH

13.0

13.0

13.0

13.0

15.1

17.2

19.2

20.9

22.6

24.2

24.8

25.4

80

SPH

10.9

11.0

11.0

10.9

13.6

16.1

18.7

20.1

21.4

22.7

23.6

24.4

85

SPH

8.9

8.9

8.9

8.9

12.0

15.1

18.2

19.2

20.2

21.2

22.4

23.5

90

SPH

8.3

8.4

8.4

8.3

10.9

13.6

16.2

17.7

19.2

20.8

21.6

22.5

95

SPH

7.8

7.8

7.8

7.8

9.9

12.0

14.1

16.1

18.2

20.2

20.9

21.7

100

SPH

7.3

7.3

7.3

7.3

9.3

11.4

13.6

15.6

17.6

19.7

20.2

20.7

105

SPH

6.7

6.7

6.7

6.7

8.8

10.9

13.0

15.0

17.1

19.1

19.4

19.8

110

SPH

*

*

*

*

6.7

8.9

10.9

13.0

15.0

17.1

18.0

18.9

115

SPH

*

*

*

*

*

6.8

8.9

10.9

13.0

15.0

16.5

18.0

LEGEND

Ewb — Entering Wet Bulb
SPH — Superheat at Compressor (F)

*Do not attempt to charge system under these conditions — refrigerant

slugging may occur.

Table 8D — Superheat Charging Table, 588A036

TEMP (F)

OUTDOOR
ENTERING

AIR

INDOOR AIR — CFM

1200

Indoor Air — Ewb (F)

54

56

58

60

62

64

66

68

70

72

74

76

65

SPH

8.4

8.4

8.4

8.4

12.5

16.7

18.7

20.7

22.0

23.4

24.8

26.1

70

SPH

5.0

5.0

5.0

5.0

9.0

13.1

15.9

18.6

20.0

21.3

22.7

24.0

75

SPH

*

*

*

*

5.4

9.6

13.1

16.6

17.9

19.3

20.6

22.0

80

SPH

*

*

*

*

*

6.0

10.3

14.5

15.9

17.3

18.6

20.0

85

SPH

*

*

*

*

*

*

7.5

12.5

13.9

15.2

16.5

17.9

90

SPH

*

*

*

*

*

*

5.4

10.4

12.5

14.6

16.8

18.8

95

SPH

*

*

*

*

*

*

*

8.4

11.3

14.1

17.0

19.8

100

SPH

*

*

*

*

*

*

*

6.4

10.0

13.5

17.1

20.7

105

SPH

*

*

*

*

*

*

*

*

8.7

13.0

17.3

21.7

110

SPH

*

*

*

*

*

*

*

*

9.3

12.4

15.6

18.7

115

SPH

*

*

*

*

*

*

*

*

10.0

11.9

13.8

15.8

LEGEND

Ewb — Entering Wet Bulb
SPH — Superheat at Compressor (F)

*Do not attempt to charge system under these conditions — refrigerant

slugging may occur.

Table 8E — Superheat Charging Table, 588A042

TEMP (F)

OUTDOOR
ENTERING

AIR

INDOOR AIR — CFM

1400

Indoor Air — Ewb (F)

54

56

58

60

62

64

66

68

70

72

74

76

65

SPH

11.0

11.0

11.0

14.0

17.0

20.0

22.0

24.0

26.0

26.0

27.7

28.6

70

SPH

7.5

7.5

7.5

10.4

13.4

16.4

18.9

21.4

24.0

25.0

26.1

27.1

75

SPH

*

*

*

6.9

9.9

12.9

15.9

18.9

21.9

23.2

24.4

25.7

80

SPH

*

*

*

5.9

8.4

10.8

13.8

16.8

19.8

21.3

22.8

24.9

85

SPH

*

*

*

5.0

6.9

8.8

11.8

14.8

17.8

19.5

21.1

22.8

90

SPH

*

*

*

*

6.0

6.8

10.2

13.7

17.3

18.6

20.0

21.4

95

SPH

*

*

*

*

*

5.0

8.7

12.7

16.7

17.8

18.9

20.0

100

SPH

*

*

*

*

*

*

6.5

10.5

14.6

16.4

18.2

20.0

105

SPH

*

*

*

*

*

*

*

8.4

12.6

15.1

17.6

20.0

110

SPH

*

*

*

*

*

*

*

8.0

12.0

14.2

16.4

18.6

115

SPH

*

*

*

*

*

*

*

7.7

11.5

13.4

15.3

17.2

LEGEND

Ewb — Entering Wet Bulb
SPH — Superheat at Compressor (F)

*Do not attempt to charge system under these conditions — refrigerant

slugging may occur.