Table 9A — Superheat Charging Table, 589A024

TEMP (F)

OUTDOOR
ENTERING

AIR

INDOOR AIR — CFM

800

Indoor Air — Ewb (F)

54

56

58

60

62

64

66

68

70

72

74

76

65

SPH

22.1

22.1

22.8

23.2

25.3

27.4

29.5

29.8

30.2

30.5

31.3

32.1

70

SPH

18.5

18.9

19.3

19.6

22.2

24.8

27.5

28.3

29.1

30.0

30.0

30.0

75

SPH

15.0

15.4

15.7

16.1

19.2

22.3

25.4

26.7

28.1

29.4

28.7

28.0

80

SPH

9.2

9.5

9.7

9.9

14.4

18.9

23.3

24.7

26.0

27.3

27.4

27.4

85

SPH

*

*

*

*

9.6

15.5

21.3

22.6

24.0

25.3

26.1

26.8

90

SPH

*

*

*

*

7.2

12.5

17.8

20.1

22.4

24.8

25.1

25.5

95

SPH

*

*

*

*

*

9.4

14.2

17.5

20.9

24.2

24.2

24.2

100

SPH

*

*

*

*

*

7.1

10.6

14.5

18.3

22.1

22.9

23.6

105

SPH

*

*

*

*

*

*

7.1

11.4

15.8

20.1

21.6

23.1

110

SPH

*

*

*

*

*

*

*

8.4

13.2

18.0

19.5

21.0

115

SPH

*

*

*

*

*

*

*

5.3

10.7

16.0

17.5

19.0

LEGEND

Ewb — Entering Wet Bulb
SPH — Superheat at Compressor (F)

*Do not attempt to charge system under these conditions — refrigerant

slugging may occur.

Table 9B — Superheat Charging Table, 589A030

TEMP (F)

OUTDOOR
ENTERING

AIR

INDOOR AIR — CFM

1000

Indoor Air — Ewb (F)

54

56

58

60

62

64

66

68

70

72

74

76

65

SPH

11.2

11.2

11.2

11.2

14.9

18.6

22.3

22.4

22.5

22.7

22.9

23.1

70

SPH

7.6

7.7

7.7

7.7

12.1

16.6

21.1

21.6

22.0

22.4

22.5

22.5

75

SPH

*

*

*

*

9.4

14.7

20.0

20.7

21.4

22.1

22.1

22.0

80

SPH

*

*

*

*

8.5

13.5

18.5

19.3

20.2

21.0

21.6

22.1

85

SPH

*

*

*

*

7.6

12.3

17.0

18.0

18.9

19.9

21.1

22.3

90

SPH

*

*

*

*

*

10.0

14.2

16.0

17.8

19.6

20.7

21.8

95

SPH

*

*

*

*

*

7.7

11.5

14.1

16.7

19.2

20.2

21.2

100

SPH

*

*

*

*

*

*

5.7

9.9

14.0

18.2

19.4

20.6

105

SPH

*

*

*

*

*

*

*

5.7

11.4

17.1

18.6

20.1

110

SPH

*

*

*

*

*

*

*

*

8.9

13.5

15.8

18.0

115

SPH

*

*

*

*

*

*

*

*

*

10.0

13.0

16.0

LEGEND

Ewb — Entering Wet Bulb
SPH — Superheat at Compressor (F)

*Do not attempt to charge system under these conditions — refrigerant

slugging may occur.

Table 9C — Superheat Charging Table, 589A036

TEMP (F)

OUTDOOR
ENTERING

AIR

INDOOR AIR — CFM

1200

Indoor Air — Ewb (F)

54

56

58

60

62

64

66

68

70

72

74

76

65

SPH

21.3

21.3

21.3

21.3

22.0

22.6

23.3

23.5

23.7

23.8

23.3

22.8

70

SPH

19.3

19.3

19.3

19.3

20.2

21.2

22.2

22.3

22.5

22.6

22.0

21.5

75

SPH

17.2

17.2

17.2

17.2

18.5

19.7

21.0

21.1

21.3

21.4

20.7

20.1

80

SPH

13.6

13.6

13.6

13.6

15.1

16.6

18.0

18.5

18.9

19.3

19.4

19.5

85

SPH

10.1

10.1

10.1

10.1

11.7

13.4

15.0

15.8

16.5

17.3

18.1

19.0

90

SPH

6.5

6.5

6.5

6.5

8.8

11.2

13.5

14.6

15.7

16.8

17.2

17.6

95

SPH

*

*

*

*

6.0

9.0

12.0

13.4

14.8

16.2

16.2

16.2

100

SPH

*

*

*

*

*

*

6.0

8.7

11.4

14.1

14.9

15.6

105

SPH

*

*

*

*

*

*

*

*

8.0

12.1

13.6

15.1

110

SPH

*

*

*

*

*

*

*

*

*

10.0

11.5

13.0

115

SPH

*

*

*

*

*

*

*

*

*

8.0

9.5

11.0

LEGEND

Ewb — Entering Wet Bulb
SPH — Superheat at Compressor (F)

*Do not attempt to charge system under these conditions — refrigerant

slugging may occur.