Table 8F — Superheat Charging Table, 588A048 (Carrier Scroll Compressor)

TEMP (F)

OUTDOOR
ENTERING

AIR

INDOOR AIR — CFM

1600

Indoor Air — Ewb (F)

54

56

58

60

62

64

66

68

70

72

74

76

65

SPH

15.5

15.5

15.6

15.6

17.6

19.6

21.6

22.8

24.0

25.2

25.2

25.3

70

SPH

11.7

11.8

11.8

11.8

13.9

16.0

18.0

20.1

22.2

24.3

24.3

24.3

75

SPH

8.0

8.0

8.0

8.0

10.2

12.3

14.5

17.4

20.4

23.3

23.3

23.3

80

SPH

6.0

6.0

6.0

6.0

8.7

11.3

13.9

16.3

18.6

20.9

21.5

22.0

85

SPH

*

*

*

*

7.2

10.3

13.4

15.1

16.8

18.5

19.7

20.8

90

SPH

*

*

*

*

5.6

7.7

9.9

12.4

15.0

17.6

18.7

19.8

95

SPH

*

*

*

*

*

5.2

6.3

9.8

13.2

16.7

17.7

18.8

100

SPH

*

*

*

*

*

*

5.8

9.1

12.5

15.8

17.1

18.4

105

SPH

*

*

*

*

*

*

5.2

8.4

11.7

14.9

16.5

18.1

110

SPH

*

*

*

*

*

*

6.2

8.8

11.4

14.0

15.9

17.8

115

SPH

*

*

*

*

*

*

7.1

9.1

11.1

13.1

15.3

17.5

LEGEND

Ewb — Entering Wet Bulb
SPH — Superheat at Compressor (F)

*Do not attempt to charge system under these conditions — refrigerant

slugging may occur.

Table 8G — Superheat Charging Table, 588A048 (Copeland Scroll Compressor)

TEMP (F)

OUTDOOR
ENTERING

AIR

INDOOR AIR — CFM

1600

Indoor Air — Ewb (F)

54

56

58

60

62

64

66

68

70

72

74

76

65

SPH

19.0

19.0

19.0

19.0

21.7

24.3

26.0

27.7

27.9

28.2

28.4

28.6

70

SPH

15.4

15.4

15.4

15.4

18.1

20.8

22.5

24.1

25.1

26.1

27.1

28.1

75

SPH

11.9

11.9

11.9

11.9

14.6

17.2

18.9

20.6

22.3

24.0

25.8

27.5

80

SPH

8.4

8.4

8.4

8.4

11.0

13.7

15.4

17.0

19.5

22.0

24.5

27.0

85

SPH

5.0

5.0

5.0

5.0

7.5

10.1

11.8

13.5

16.7

20.0

23.2

26.4

90

SPH

*

*

*

*

*

6.6

9.0

11.4

14.7

17.9

21.1

24.4

95

SPH

*

*

*

*

*

*

6.2

9.4

12.6

15.9

19.1

22.3

100

SPH

*

*

*

*

*

*

*

7.3

10.6

13.8

17.0

20.3

105

SPH

*

*

*

*

*

*

*

5.3

8.5

11.8

15.0

18.2

110

SPH

*

*

*

*

*

*

*

*

6.9

11.2

15.5

19.8

115

SPH

*

*

*

*

*

*

*

*

5.3

10.6

16.0

21.3

LEGEND

Ewb — Entering Wet Bulb
SPH — Superheat at Compressor (F)

*Do not attempt to charge system under these conditions — refrigerant

slugging may occur.

Table 8H — Superheat Charging Table, 588A060

TEMP (F)

OUTDOOR
ENTERING

AIR

INDOOR AIR — CFM

1995

Indoor Air — Ewb (F)

54

56

58

60

62

64

66

68

70

72

74

76

65

SPH

20.1

20.1

20.1

20.1

20.1

20.1

22.6

25.2

25.6

26.1

26.6

27.0

70

SPH

16.5

16.5

16.5

16.5

17.3

18.0

20.6

23.1

24.0

24.8

25.6

26.5

75

SPH

13.0

13.0

13.0

13.0

14.5

16.0

18.5

21.1

22.3

23.5

24.7

25.9

80

SPH

10.9

10.9

10.9

10.9

12.4

13.9

16.5

19.0

20.6

22.2

23.8

25.4

85

SPH

8.9

8.9

8.9

8.9

10.4

11.9

14.4

17.0

18.9

20.9

22.9

24.9

90

SPH

6.9

6.9

6.9

6.9

8.4

9.9

12.4

14.9

17.3

19.6

22.0

24.3

95

SPH

5.0

5.0

5.0

5.0

6.3

7.8

10.3

12.9

15.6

18.3

21.1

23.8

100

SPH

*

*

*

*

*

5.8

8.3

10.8

13.9

17.0

20.1

23.2

105

SPH

*

*

*

*

*

*

6.2

8.8

12.3

15.7

19.2

22.7

110

SPH

*

*

*

*

*

*

*

6.7

10.6

14.4

18.3

22.2

115

SPH

*

*

*

*

*

*

*

*

8.9

13.1

17.4

21.6

LEGEND

Ewb — Entering Wet Bulb
SPH — Superheat at Compressor (F)

*Do not attempt to charge system under these conditions — refrigerant

slugging may occur.