4 step 2: parameterising the application – Lenze E94AxHE Technology Application Actuating drive - Speed User Manual

Page 12

Advertising
background image

9400 Technology applications | Actuator – speed

Short setup

Step 2: Parameterising the application

12

L

EDS94TA10010xxxx EN 1.1 - 10/2008

3.4

Step 2: Parameterising the application

For parameterising the application in the »Engineer«, use the Application parameters tab

which will be displayed by default when selecting the controller in the project view:

1. Select the mains voltage (C00173).
2. If a brake is used: Activate automatic brake control via brake module

(C02580 = "Autom. with brake module").

3. Select the deceleration time for quick stop (C00105), e.g. "0.1 s".

– If digital input DI1 is set to LOW level, the drive is decelerated to standstill within the

quick stop deceleration time independently of the setpoint selection.

4. Select the deceleration time for stop (C02610), e.g. "0.5 s".

– If the speed follower is inhibited by resetting digital input DI2 to LOW level, the drive

is decelerated within the deceleration time for stop.