EDS94TA10010xxxx EN 1.1 - 10/2008

L

19

9400 Technology applications | Actuator – speed

Parameter setting & configuration

Speed setpoint conditioning

4.3.1

Change-over to fixed setpoint

[4-3]

Additional offset for the speed limit value (schematic diagram)

Via the digital input DI4 a change-over to a parameterisable fixed setpoint can take place.

r

Parameter setting: Tab Application parameters  dialog level Overview

Use of further fixed setpoints
A total of 15 different fixed setpoints can be parameterised. For the selection of the fixed

setpoints 2 ... 15 the selection inputs are to be assigned with the corresponding signals.

The selection of the fixed setpoints is carried out in a binary coded manner.

r

Parameter setting: Tab Application parameters  dialog level Overview  Ramp

generator  All fixed setpoints

Gain

Invert setpoint

Selection

LS_Speed...

M

Speed
setpoint

DI2

DI3

DI4

OUT

IN

Ramp generator

%

1

%

2

%

15

Fixed setpoints

Status

machine

(basic drive

functions)

Speed setpoint

AIN1

M

v

Parameter

Lenze setting

Value Unit

C03500/1

Fixed setpoint 1

10.00 %

Control inputs of the function

Signal configuration

Lenze setting

Control input

(Multiplexer parameters)

DIGIN 4  Activate fixed setpoint 1

C03009/4

Parameter

Lenze setting

Value Unit

C03500/1

Fixed setpoint 1

10.00 %

C03500/2

Fixed setpoint 2

0.00 %

C03500/...

Fixed setpoint ...

... ...

C03500/15

Fixed setpoint 15

0.00 %

Control inputs of the function

Signal configuration

Lenze setting

Control input

(Multiplexer parameters)

DIGIN 4  Activate fixed setpoint 1

C03009/4

FALSE  Activate fixed setpoint 2 a

C03009/5

FALSE  Activate fixed setpoint 4 a

C03009/6

FALSE  Activate fixed setpoint 8 a

C03009/7