Page 15 – Practical Instrument Electronics 820-ELITE User Manual

Page 17

Advertising
background image

Page 15

READ

%

PWR MEASURE

28.20

SOURCE

HI

SET

LO

OFF

MAX
READ

MIN

READ

OVERLOAD

Hz SYNC

Double Click

Menu

Push & Turn

for

Fast Dialing
Push & Hold

to

Store/Step

mA ∙ V ∙ pH ∙ TC ∙ Ω ∙ RTD ∙ Freq ∙ Pressure

Typical

2-Wire

Transmitter

+ IN -

REF +OUT-

Transmitter Input

Sensor

Process Signal

Simulated Input

SOURCE

HI

SET

LO

MAX
READ
MIN

READ

Power/Measure mA, Power/Measure % (Percent of 4 to 20 mA)

Choose this function to simultaneously supply power to a 2 Wire
Transmitter while displaying the 4.000 to 20.000 mA output of
the transmitter.

Move the power switch

w

to READ then Double Click the

EZ-DIAL knob to get into the Double Click Menu. Turn the knob

e

to scroll through the settings and press the knob to make your

selection. Select mA for the FUNCTION and PWR MEAS for the
MODE. Choose either mA or % and whether you need the 250

HART resistor active in the loop.

Disconnect one or both input wires from the device to be
calibrated. Connect the red source lead of the PIE 820-ELITE to
the plus (+) input of the device and the black source lead to the
minus (-).

The PIE 820-ELITE supplies a nominal 24 volts DC at 24 mA to
the 2 Wire Transmitter. The current passed by the transmitter will
be accurately displayed by the PIE 820-ELITE. Calibrate the
transmitter in the usual manner and disconnect the PIE
820-ELITE. Signals above 24 mA are current limited by protection
circuitry with “OVERRANGE” flashed on the display and the red
OVERLOAD LED lit.