Control the Drive

Enable Keypad Control to Start the Drive

The CopyCat Keypad can be used to program and control drive operation. The Stop
key is always active, but you must enable Start and direction of rotation keys.

1. Press the Escape key until the Program LED lights.

2. Use the Up or Down arrow key to scroll to P46 - [Input Mode].

Or
Enter 46 using the numeric keys and press the Enter key.

3. Press the Select key to edit the parameter value.

4. Change P46 - [Input Mode] to 2 or 6.

For detailed information regarding parameter settings, please refer to the 160
SSC™ Variable Speed Drive (Series C) User Manual, Publication 0160-5.15

5. Press the Enter key to save the new value.

Save Changes to Parameter 46

In order for changes to P46 - [Input Mode] to take effect, cycle power or set
P56 - [Reset Function] to 2

1. Use the Up or Down arrow key to scroll to P56 - [Reset Function].

Or
Enter 56 using the numeric keys and press the Enter key.

2. Press the Select key to edit the parameter value.

3. Change P56 - [Reset Function] to 2.

4. Press the Enter key to save the new value.

The new P46 - [Input Mode] value is saved and P56 - [Reset Function] resets to 0.

You can now use the CopyCat Keypad to start the drive.

Important:

The Stop/Reset digital input must be maintained in the ON state
for the keypad to start the drive.