STC Starting Torque Controller

1-3

Features

The STC controller is a compact device with feed through wiring for
ease of installation. To set up the controller, adjust the digital rotary
switches. The initial torque value is set between 10 and 80% of
locked rotor torque. The voltage ramp time is adjustable from 0.1 to
4.5 seconds. This flexible combination enables the STC controller to
be installed in a wide variety of applications.

Adjustments

Figure 1.5 STC Controller Adjustments

Table 1.A

Initial Torque Level (Nominal)

Table 1.B

Voltage Ramp Time (Nominal)

(With Initial Torque Set At 0)

T1

2

T2

4

T3

6

Digital Rotary switches for easy adjustments

Position

0

1

2

3

4

5

6

7

8

9

% of Locked

Rotor Torque

10

15

20

25

30

40

50

60

70

80

Position

0

1

2

3

4

5

6

7

8

9

Time

(Seconds)

0.1

0.5

1.0

1.5

2.0

2.5

3.0

3.5

4.0

4.5