Wiring diagram with interface option – Rockwell Automation 150 MNL/SMC DIALOG+/APP-PROD GUIDE User Manual
Page 28
Advertising
SMC-2 Smart Motor Controller
2-9
Wiring Diagram with Interface Option
Control power requirement for the interface option is 5VA at 120V
and 15VA at 240V. Auxiliary contact rating is NEMA C300, 2.5
Amps, 20–250V AC: 1 Amp, 12–30V DC.
Figure 2.11 Wiring Diagram with Interface Option
3-Phase
Power Input
Branch
Protection ➀
Overload Relay
(O.L.)
➀
C.C.T. ➀
O.L. ➀
➀ Customer supplied
Maximum fuse size 10A, 250V.
For two wire control, remove stop/start push buttons and
connect two wire device between terminals 1 0 a n d 3 0
➁
➂
Auxiliar
Contact
Stop ➀ ➂
Start
➀
SMC-2 Controlle
Interface Option
L1/1
L2/3
L3/5
T1/2
T2/4
T3/6
Motor
➀
➀
10
20
30
40
50
60