SMC Dialog Plus Smart Motor Controller

Adjustments (cont.)

Full Voltage Start without Options

The SMC Dialog Plus controller may be programmed to provid
full voltage start in which the output voltage to the motor reaches full
voltage in 1/4 second.

Parameter

Range

Start Mode

This must be programmed for “Soft Start.”

Soft Start, Current Limit

Ramp Time #1

This must be programmed for “0” seconds.

0 to 30 seconds

Initial Torque #1

This must be programmed for 90% of locked
rotor torque.

0 to 90% of locked rotor torque

Kickstart Time

This must be programmed for “0” seconds.

0.0 to 2.0 seconds

Stall Delay

Allows the user to program the stall protection
delay time. The delay time begins after the
start time has timed out.

0 to 10 seconds

Energy Saver

The Energy Saver feature monitors the motor
load, phasing back the voltage output to the
motor when the motor is lightly loaded or
unloaded for an extended period of time.

Off, On

Aux Contacts 1&2

Two form C contacts are provided as standard
with the SMC Dialog Plus controller. These
contacts are located at terminals 18, 19, and
20. Aux Contacts 1&2 allows the user to
configure the operation of the contacts.

Normal, Up-to-speed

Aux Contact 3

A third auxiliary contact is provided between
terminals 29 and 30. Aux Contact 3 allows the
user to program the operation of the contact.

Normal, Fault

Contact 3 Config

This parameter provides the user with the
ability to program the “powered-up” state of
the third auxiliary contact.

N.O., N.C.

Parameter Mgmt

The newly programmed parameters values can
be saved to memory, or the factory default
parameter values can be recalled.

Ready, Default Init., Recll Frm EE,
Store In EE