Reference

10-5

kVA per Horsepower is Calculated as Follows:

For three-phase motors:

For single phase motors:

Table 10.

NEMA Locked-Rotor Current Code Letters

Locked-rotor kilovolt -amperes-per-horsepower range includes the lower figure up to, but not
including, the higher figure (i.e., 3.14 is letter “A” and 3.15 is letter “B”).

Letter Designation

kVA per HP

A

0–3.15

B

3.15–3.55

C

3.55–4.0

D

4.0–4.5

E

4.5–5.0

F

5.0–5.6

G

5.6–6.3

H

6.3–7.1

J

7.1–8.0

K

8.0–9.0

L

9.0–10.0

M

10.0–11.2

N

11.2–12.5

P

12.5–14.0

R

14.0-–6.0

S

16.0–18.0

T

18.0–20.0

U

20.0–22.4

V

22.4 and up

kVA/HP

1.73

Current (in Amperes)

×

Volts

×

1,00

0H

×

-------------------------------------------------------------------------

=

kVA/HP

Current (in Amperes)

Volts

×

1,00

0H