SMC Dialog Plus Smart Motor Controller

3-19

Control Options

The SMC Dialog Plus controller offers a variety of unique control
options that provide enhanced motor starting and stopping
capabilities. Please note that the options are mutually exclusive and
must be specified at the time of order entry.

Soft Stop

Pump Control

Preset Slow Speed

SMB

Smart Motor Braking

Accu-Stop

/Slow Speed with Braking

Soft Stop Option

The Soft Stop option can be used in applications requiring an
extended coast-to-rest. The voltage ramp down time is use
adjustable from 0 to 60 seconds. The Soft Stop time is adjusted
independently from the start time. The load will stop when the
voltage drops to a point where the load torque is greater than th
motor torque.

Figure 3.16 Soft Stop Option

Start

Run

Soft Stop

Coast-to-rest

Soft
Stop

Kickstart

Initial

Torque

100%

Percent

Voltage

Time (seconds)

!

ATTENTION: Soft Stop is not intended to be used as
an emergency stop. Refer to the applicable standards for
emergency stop requirements