SMC-2 Smart Motor Controller

Modes of Operation (cont.)

Soft Start

This is the most common method of starting. The initial torque value
is set between 0–70% of locked rotor torque. The motor voltage is
steplessly increased during the acceleration ramp period, which is
adjustable from 2–30 seconds.

Figure 2.2 Soft Start

Current Limit Start

This starting mode is used when it is necessary to limit the maximum
starting current. This can be adjusted from 25 to 550% of full load
amperes. The current limit starting time is customer set. If the motor
is not up to speed after the selected time, the motor will transition to
full voltage

Figure 2.3 Current Limit Start

Start Run

Percent

Voltage

Initial

Torque

100%

Time (seconds)

Start

550

25

Percent

Full Loa

Amp

Time (seconds)