SMC Dialog Plus Smart Motor Controller

3-27

Preset Slow Speed Option

The Preset Slow Speed option can be used on applications that require
a slow speed for positioning material. The Preset Slow Speed can be
set for either Low, 7% of base speed, or High, 15% of base speed.
Reversing is also possible through programming. Speeds provided
during reverse operation are Low, 10% of base speed, or High, 20%
of base speed.

Figure 3.22 Preset Slow Speed Option

Forward

15% – Hig

7% – Low

10% – Low

20% – High

Reverse

Run

Start

Time (seconds)

!

ATTENTION: Slow speed running is not intended fo
continuous operation due to reduced motor cooling.

Advertising