5-12

SMC Dialog Plus Controller Special Application Considerations

SMC Dialog Plus Controller
as a Bypass to an AC Drive

By using the controller as shown in Figure 5.9, a soft star
characteristic can be provided in the event that an AC drive is non-
operational.

Note: A controlled acceleration can be achieved with this scheme,

but speed control is not available in the bypass mode.

Figure 5.9 Typical Application Diagram of a Bypass Contactor for an AC

Drive

!

ATTENTION: Proper care must be taken to isolate th
AC drive from line and load potential when the
controller is energized.

➀ Mechanical interlock required.

Custom er supplied.

Many VF drives are rated 150% FLA. Because the SMC Dialog Plus controller can be

used for 600% FLA starting, separate branch circuit protection m ay be required.

Overload protection is included as a standard feature of the SMC Dialog Plus controller.

Pow er Input

VFD Branch
Protection ➂

SMC Dialog Plus Controller

L1/1

L2/3

L3/5

T1/2

T2/4

T3/6

Motor

VFD

3-Phase

O.L.➁