SMC Dialog Plus Smart Motor Controller

3-9

Control Terminal Description

The SMC Dialog Plus controller contains 20 control terminals on the
front of the controller. These control terminals are described below.
See Figure 3.11.

Power Supply Board

Logic Board

Figure 3.11 SMC Dialog Plus Controller Control Terminals

Terminal Number

Description

11

Control Power Input

12

Control Power Common

13

Controller Enable Input

14

Logic Ground

15

Dual Ramp/Option Input

16

Start Input

17

Stop Input

18

Auxiliary Relay Common

19

N.O. Auxiliary Contact 1 (Normal/Up-to-speed)

20

N.C. Auxiliary Contact 2 (Normal/Up-to-speed)

Terminal Number

Description

21

Not Used

22

Not Used

23

Not Used

24

Not Used

25

Common (Converter Module)

26

Phase A Input (Converter Module)

27

Phase B Input (Converter Module)

28

Phase C Input (Converter Module)

29

N.O./N.C. Auxiliary Contact 3 (Normal/Fault)

30

N.O./N.C. Auxiliary Contact 3 (Normal/Fault)