Rockwell Automation 1400-SP PowerMonitor Software User Manual

Page 18

Advertising
background image

Chapter 3
Installation

3–4

!

ATTENTION: Never connect an RS–232C equipped
device to the DATA+ or DATA– lines of an RS–485
equipped communication system. Doing so will damage
the RS–485 driver circuits of every device within the site.

!

ATTENTION: Converters such as the Catalog Number
1400–CC converter must always be used between devices
that use RS232C/RS–485 communications standards.

If the computer running the Powermonitor Software uses an RS–232C serial
port in conjunction with an external Catalog Number 1400–CC RS–232C to
RS–485 converter, then install a straight 25–conductor RS–232C cable or a
cable configured with (3) wires to pins 2, 3, and 7 from the desired serial port
at the back of the computer to the RS–232C input on a Catalog Number
1400–CC converter. The DATA+ and DATA– lines on the RS–485 side of
the converter are then connected to the DATA+ and DATA– on each
Powermonitor via a shielded two–wire twisted pair cable as shown in
Figure 3.2.

Important: Be sure to connect both ends of the shield between devices.

Figure 3.2
RS–485 Communications Connections – External Converter

RS–232C

Port

IBM PC (DTE)

+

+

RS–232C

External RS–232C to

RS–485 Converter

SHIELD

SHLD

To other

devices

Bulletin 1400–CC

SHIELD

SHIELD

150Ω

Resistor

25 Pin

Male

Connector

(DB 25)

25 Pin

Female

Connector

(DB 25)

+

SHLD

Power–

monitor

#1

Power–

monitor

#2

Power–

monitor

#3

150Ω

Resistor

+

SHLD

SHLD

Advertising