Save disk, Snapshot log – Rockwell Automation 1400-SP PowerMonitor Software User Manual

Page 46

Advertising
background image

Chapter 5
Powermonitor Data Display and Configuration

5–8

Viewing of the entire log is accomplished by moving the highlight bar with
the arrow keys, the Page Up or Page Down keys, or the Home or End keys.

Save Disk

Pressing the F7 key while displaying the EVENT LOG will save the present
contents of the log to a disk file in the present directory. The log file can
then be printed out as described in Chapter 7.

The Powermonitor implements a snapshot log that allows the device to store
the historic values of Volts, Amps, kW, kVAR, kW Demand, Amp Demand,
Power Factor, Vaux, Frequency, kWH, kVARH, and kWH Reverse at
user–defined intervals ranging from 1 second to 400 days.

The SNAPSHOT LOG screen displays a record of device snapshots that
have been up loaded by the Powermonitor Software. Since there is a large
amount of information to display, the snapshot information is divided and
displayed on three screens: left, center, and right. Examples of the three
SNAPSHOT LOG screens are shown in Figure 5.6 through Figure 5.8.

Figure 5.6
Snapshot Log (Left) Screen

Snapshot Log

Advertising