Chapter 5
Powermonitor Data Display and Configuration

5–16

The SETPOINT/RELAY SETUP screen (shown in Figure 5.12) is displayed
when the operator selects SETPOINT/RELAY SETUP for the Powermonitor.
It allows the operator to display or change the programmable setpoint/relay
parameters of any Powermonitor.

Figure 5.12
Setpoint Screen

Setpoint Parameter Descriptions

Brief notes on modifying each parameter are provided below. Refer to
Publication 1400–800, ‘‘Bulletin 1400 Powermonitor Installation and
Operation Manual,” for detailed descriptions of all setpoint parameters.

a. SETPOINT TYPE. Press the plus or minus keys to advance

through the available setpoint types.

b. HIGH AND LOW LIMITS. Numbers entered into these fields

must lie within the range from 0 to 999999. Values outside this
range will be rejected.

Important: High/Low limits for Under/Over Frequency must be entered as
the value x 10. For example, 60.5 Hz would be entered as 605.

c. TIME DELAY OPERATE AND TIME DELAY RELEASE.

Valid time delay values for both parameters range from 0 to 32000.

d. RELAY NUM. Press the plus or minus keys to toggle between the

valid relay numbers. A relay number of 0 indicates that no relay is
to be assigned to the setpoint.

Refer to Publication 1400–800, ‘‘Bulletin 1400 Powermonitor Installation
and Operation Manual,” for additional information pertaining to the
operation of the setpoint functions.