Logging of relay control commands, Manual relay operations – Rockwell Automation 1400-SP PowerMonitor Software User Manual

Page 58

Advertising
background image

Chapter 6
Manual Control of Powermonitor Relays

6–2

The Event Logs of Powermonitors will log only commands which they
respond to. Powermonitors will not log relay commands which are ignored
due to the conditions outlined above.

To manually operate a Powermonitor relay, select the OPERATE RELAY
function by selecting the RELAY CONTROL option from the MAIN
MENU. This will display the RELAY CONTROL SCREEN as shown in
Figure 6.1.

Figure 6.1
Relay Control Screen

Upon entry to this screen, the user is required to enter the Powermonitor
Software password. Failure to enter the correct password will cause
Powermonitor Software to exit the RELAY CONTROL SCREEN and return
to the MENU screen.

After pressing <Enter>, the user is asked what operation to perform on the
selected relay. Valid operations are:

a. 1 – NORMAL. This operation will cause the control of the

indicated relay to return to the device setpoints if the relay is in
latch mode.

This command has no effect if the relay is in any pulse mode.

b. 2 – FORCED ON. This operation will cause the indicated relay

number to operate. if the relay is in latch mode, or pulse if the relay
is in pulse mode.

Logging Of Relay Control
Commands

Manual Relay Operations