Chapter 2
Introduction and Product Description

2-2

Board Configuration

The Node Adapter Board causes the Bulletin 1395 Drive to appear as a
remote I/O rack to the PLC Controller. Data transfer between the PLC
Controller and Drive (at the PLC level) is the same as if the PLC
Controller were transferring data to a remote I/O rack. The rack structure
consists of two specific types : full or half rack. A full rack is defined as an
8 group rack, while a half rack is defined as a 4 group rack. Each group,
whether in a full or half rack configuration contains 16 input and 16 output
bits, which are mapped directly into the PLC Controller I/O image table
(refer to Chapter 3 for a description of data transfer). Refer to Figure 2.1
and Figure 2.2 for further information on the full and half rack
configurations.

Figure 2.1
Full Rack Configuration

GROUP 0

GROUP 1

GROUP 2

GROUP 3

GROUP 4

GROUP 5

GROUP 6

GROUP 7

Reserved for

Block Transfer

Module

Groups 1 – 7 each appear to have a 16 bit

input and a 16 bit output module in place

Figure 2.2
Half Rack Configuration

GROUP 0

GROUP 1

GROUP 2

GROUP 3

GROUP 4

GROUP 5

GROUP 6

GROUP 7

Reserved for

Block Transfer

Module

Groups 1 – 3 each appear to have a 16 bit

input and a 16 bit output module in place

Reserved for

Block Transfer

Module

Groups 5 – 7 each appear to have a 16 bit

input and a 16 bit output module in place