Chapter 3
Functional Description

3-10

The board calculates the message length before returning a reply to the
PLC Controller.
Depending on the action requested by the block transfer function, the
message length contained in this byte may or may not be the same when
returned from the Node Adapter Board.

Table 3.A
Block Transfer Message Word 3 – Code Definitions

Class

Element (HEX)

Word 3 (Decimal)

01 EE Memory Request

01 Recall

257

02 Store

513

03 Initialize

769

02 Read Request

02 Variable/Parameter Value

514

03 Variable/Parameter Full (value, min, max dec, text)

770

04 Read System Clock

1026

06 Fault Code with Primary Fault Text

1538

03 Write Request

02 Parameter value

515

04 Write System Clock

1027

06 Reset Drive*

1539

07 Clear Faults

1795

04 Configuration Request

01 Upload Configuration Table (#50–69)

260

02 Upload Configuration Table (#150–169)

516

03 Upload Configuration Table (#250–269)

772

04 Upload Configuration Table (#350–369)

1028

05 Upload Configuration Table (#450–469)

1284

06 Download Configuration Table (#50–69)

1540

07 Download Configuration Table (#150–169)

1796

08 Download Configuration Table (#250–269)

2052

09 Download Configuration Table (#350–369)

2308

0A Download Configuration Table (#450–469)

2564

0E Trend Upload

01 Read Trend File

270

* No return response for BT

Table 3.B
Block Transfer Status Byte (Word 4, High Byte)

Decimal

11

10

9

8

PLC / Octal

13

12

11

10

0

0

0

0

SUCCESSFUL

0

0

0

1

MESSAGE I.D. ERROR

0

0

1

0

ILLEGAL REQUEST

0

0

1

1

NOT USED

0

1

0

0

ILLEGAL PARAMETER

0

1

0

1

ROUTE ERROR

0

1

1

0

IGNORED BECAUSE OF MODE

0

1

1

1

NOT USED

1

0

0

0

OUT OF RANGE

1

0

0

1

EXECUTION MALFUNCTION