Chapter 3
Functional Description

3-4

Similarly, the External Velocity Ref (Parameter 154) has been linked to
source Parameter 301. The 16 bit output word for group 2 of rack 2 must
be a 16 bit signed integer whose value corresponds to the allowable values
in drive units for Parameter 154.

Information from the drive consists of Logic Status (Parameter 100) and
Velocity Fdbk (Parameter 106). Based on the links shown in Figure 3.2, the
16 bit input word for group 1, rack 2 in the PLC Controller is a 16 bit logic
status word. The bits in this 16 bit word are defined by the description for
Parameter 100. In addition, the 16 bit input for group 2, rack 2 in the PLC
Controller is a 16 bit signed integer whose value corresponds to the
allowable values in drive units for Parameter 106.

Figure 3.2
Discrete PLC Controller I/O Example

Port B Interface

300

PLC (Rack 2)

Output Image Table

Group 0

Group 1

Group 2

Group 3

Group 4

Group 5

Group 6

Group 7

Input Image Table

Bulletin 1395 Drive

301

150

Sinks

151

152

154

156

157

100

101

106

112

350

351

Group 0

Group 1

Group 2

Group 3

Group 4

Group 5

Group 6

Group 7

Port B

Sources

Port B

Sinks

Logic Cmd 1

Logic Cmd 2

Logic Cmd 3

External Vel Ref

Tach Velocity

External Torque Ref

Logic Status

Drive Status

Velocity Fdbk

Arm Current Fdbk

Sources