Chapter 6
Troubleshooting and Maintenance

6-2

Certain fault conditions in the Bulletin 1395 can be configured in terms of
their Soft or Warning Fault nature. That is, the user/operator may specify
the action taken, either Soft Fault or Warning Fault (Report Only).

ATTENTION: Ignoring faults that have been configured as
Report Only could damage certain components in the drive.

Examples of Soft/Warning Faults configurable by users are:
S Motor Overtemperature
S AC Line Out of Tolerance
S Heat Sink Overtemperature

Node Adapter Fault Messages

The fault messages available on the Discrete Adapter Board are:
S NA-01 – NODE ADAPTER – PROCESSOR OK

Default state, no error exists.

S NA-02 through NA-05 – NOT USED

Reserved for future use.

S NA-06 – HANDSHAKE TIMEOUT

Communication malfunction between Node Adapter Board and Main
Control Board. Replace Adapter Board, replace Main Control Board.

S NA-07 – NOT USED

Reserved for future use.

S NA-08 – NO COMSOF

Communication malfunction between Node Adapter Board and PLC
Controller. Check wiring, PLC Controller, replace Adapter Board.

S NA-09 – ILLEGAL MODE SEQUENCE

Incorrect mode detected. Replace Main Control Board, replace Node
Adapter Board.

S NA-10 – NO INPUT IMAGE

Communication malfunction between Node Adapter Board and PLC
Controller. Check wiring, PLC Controller, replace Adapter Board.

S NA-11 – OUTPUT IMAGE LOST

Communication malfunction between Node Adapter Board and PLC
Controller. Check wiring, PLC Controller, replace Adapter Board.

S NA-12 – SIU BUFFER OVERFLOW

Communication malfunction between Node Adapter Board and PLC
Controller. Check wiring, PLC Controller, replace Adapter Board.

S NA-13 – PLC COMMAND ILLEGAL

Communication malfunction between Node Adapter Board and PLC
Controller. Check wiring, PLC Controller, replace Adapter Board.