Chapter 3
Functional Description

3-7

Due to the fact that bit numbering in the PLC Controller is done in Octal,
as opposed to decimal numbering in the drive Parameter 150, it is
necessary to relate the output image table bits to the controlled bits in
Parameter 150. Figure 3.4 shows the correlation between the output image
table bits and the drive Parameter 150 bits. As a result of this relationship,
if it is desired to set the start bit in Parameter 150 (bit 12 decimal), than bit
021/14 must be set as shown in the first rung of Figure 3.3. Control of
other logic bits is illustrated in Figure 3.3.

Figure 3.4
Discrete PLC Controller I/O Example

Port A Interface

300

PLC Controller (Rack 2)

Output Image Table

Group 0

Group 1

Group 2

Group 3

Group 4

Group 5

Group 6

Group 7

150

Sinks

Port B

Sources

Logic Cmd 1

0 : 21

00
01
02
03
04
05
06
07
10

11

12
13
14
15
16
17

P150

00
01
02
03
04
05
06
07
08
09
10

11

12
13
14
15

Run Reference Select A

MOP Increment

MOP Decrement

Ramp Disable

MOP Rate 1
MOP Rate 2

Command Enable

Jog 2
Jog 1

Normal Stop

Start

Close Contactor

Clear Fault

Process Trim Enable

Run Reference Select B
Run Reference Select C