Upload Configuration Table
This function uploads the configuration table information from the Drive in
blocks. Each block of configuration data has a separate function code.
PLC Block Transfer Data –
BTW Instruction Length: 4
BTR Instruction Length: 40
BTW Message Structure –
Message Header Information:
Word 1: 0
Word 2: 0
Function Code, Word 3: see table below
Write Message Length, Word 4: 8 bytes
WORD
BTW (SETUP)
Upload Function Codes
1
2
3
4
0
0
See Table Above
8
Parameter Numbers
#50 – #69
#150 – #169
Function Code
#250 – #269
#350 – #369
#450 – #469
260
516
772
1028
1284