Rockwell Automation Publication 1794-UM010D-EN-E - July 2013

9

Overview of the Very High Speed Counter Module

Period/Rate Mode

In Figure

Period/Rate Mode on page 9

, the incoming pulse train from the gate/

reset terminal is used to sample pulses from the 5 MHz internal clock. As the
frequency of the incoming pulse train at the gate/reset terminal increases, the
number of sampled pulses from the 5 MHz clock decreases. This relationship is
shown in NO TAG. Since accuracy is related to the number of pulses received
over the sample period, the accuracy will decrease with increasing input
frequencies at the Gate/Reset terminal.

To some extent, the decrease in accuracy can be lessened by scaling the input
frequency through the use of a scaler. A scaler value of 1 will only return an
accurate input frequency if incoming pulses have a 50% duty cycle.

Incoming pulse train at Z
(gate/reset terminal)

5 MHz internal clock

A (not used)

B (not used)

Input A

Input B

Single phase pulse generator

1794-VHSC

Input Z
scaler
5 MHz clock

1

Accumulated count

Frequency and outputs
updated here

10

20

Z (gate/reset)

Assumes symmetrical pulse, 50% duty cycle, so period = sample time on X 2 (on and off)
Frequency = 1/period
If count = 25, scaler = 1, and clock period = (1/5 MHz)
Frequency = 1 / [(25/1) X (1/5 MHz) X 2] = 100 KHz

45893

Relationship Between Sampled Pulses and Input Frequency

Input Frequency at Z
(Gate/Reset)
Terminal in Hz

Sampled Pulses for 1/2 Cycle of Z
(Gate/Reset) Pulse

2

1.25M

5

500K

10

250K

20

125K

50

50K

100

25K