Rockwell Automation 1794-VHSC 1794 FLEX I/O Very High Speed Counter Module User Manual User Manual

Page 60

Advertising
background image

50

Rockwell Automation Publication 1794-UM010D-EN-E - July 2013

Specifications

Current, on-state, max

5V DC terminations: 0.5 A
12…24V DC terminations: 1.0 A

Current per
output pair, max

5V DC terminations: 0.5 A
12…24V DC terminations: 1.0 A

Short circuit current

5V DC terminations: 0.9A
12…24V DC terminations: 4.0A
Outputs are short-circuit protected and turned off until power is cycled.

Surge current

2A for 50 ms, repeatable every 2 s

Delay Time
Off to On
On to Off

25

μ

s (load dependent)

150

μ

s (load dependent)

General Specifications

Attribute

Value

Module location

1794-TB3G and 1794-TB3GS

External DC power supply
voltage range, nom

24V DC

Supply voltage

19.2…31.2V DC (includes 5% AC ripple)

Supply current

100 mA @ 24V DC

Dimensions, HxWxD
(with module installed on
terminal base)

94 x 94 x 69 mm
(3.7 x 3.7 x 2.7 in.)

Isolation voltage

50V (continuous), Basic Insulation Type, between six isolated areas
including:
FlexBus
Module 24V DC power
A0/B0/Z0 inputs
A1/B1/Z1 inputs
00/01 and output power supply 1
02/03 and output power supply 2
Tested @ 850V DC for 1 s

FlexBus current

75 mA @ 5V DC (with terminal base power off)

Power dissipation, max

5.0 W @ 31.2V DC

Thermal dissipation, max

17.1 BTU/hr @ 31.2V DC

Indicators
(field side driven, logic
side indication)

1 green/red power/status indicator
6 yellow input status indicators – logic side
4 yellow output tatus indicators – logic side

Keyswitch position

1

Output Specifications

Attribute

Value

Advertising