I/o structure, Adapter input status word – Rockwell Automation 1794-VHSC 1794 FLEX I/O Very High Speed Counter Module User Manual User Manual

Page 39

Advertising
background image

Rockwell Automation Publication 1794-UM010D-EN-E - July 2013

31

Communicate With Your Module

If the configuration is considered acceptable, the counter application specific
integrated circuit (ASIC) is disabled — counting is suspended and outputs are
shut off — while the ASIC is loaded with the new operational parameters.

I/O Structure

Output data is received by the adapter in the order of the installed I/O modules.
The Output data for Slot 0 is received first, followed by the Output data for Slot
1, and so on up to slot 7.

The first word of input data sent by the adapter is the Adapter Status Word. This
is followed by the input data from each slot, in the order of the installed I/O
modules. The Input data from Slot 0 is first after the status word, followed by
Input data from Slot 2, and so on up to slot 7.

Adapter Input Status Word

The input status word consists of:

• I/O module fault bits — 1 status bit for each slot
• node address changed — 1 bit
• I/O status — 1 bit

Adapter Status

Read

Write

Slot 0 Input Data

Slot 1 Input Data

Slot 7 Input Data

Adapter Status

Slot 0 Output Data

Slot 1 Output Data

Slot 7 Output Data

EtherNet/IP adapter

Slot 0

Slot 1

Slot 7

45901

I/O Module Fault Bits

Not used

Node Address Changed Bit

Bit:

15

0

14

13

12

11

10

9

8

7

6

5

4

3

2

1

Slot 0

Slot 1

Slot 2

Slot 3

Slot 4

Slot 5

Slot 6

Slot 7

Node Address Changed Bit

Created by controller

{

45902