10

Rockwell Automation Publication 1794-UM010D-EN-E - July 2013

Overview of the Very High Speed Counter Module

Operation of Scaler

In period/rate mode, the scaler lets the incoming pulse train at the Z (gate/reset)
terminal be divided by a user defined number. Acceptable values for the scaler are
1, 2, 4, 8, 16, 32, 64 and 128. There is one scaler value for each counter.

Connection to Counter Inputs

The only input to the module in the period/rate mode is made to the Z (gate/
reset) terminal. The counter inputs (channel A and B) are not used in the period/
rate mode.

Continuous/Rate Mode

The continuous/rate mode is similar to the period/rate mode previously
described except the outputs in this mode are dynamic outputs. Use this mode to
determine the frequency of input pulses by counting the number of internal
5 MHz clock pulses over a user-specified number of input signal pulses. Each
output is turned on as soon as the turn-on count is reached, and turned off as
soon as the turn-off count is reached. As the internal 5 MHz clock is counted, the
outputs dynamically track the 5 MHz count. This allows you to turn an output
on a certain number of 5 MHz counts after the gate/reset pin goes active, and
turn it off a certain number of 5 MHz counts later.

1794-VHSC module counts the total number of pulses occurring at the Z (gate/
reset) terminal. This function is frequency-limited to 200 Hz X the scaler value.
This total count is returned in input file words 4 (LSW) and 5 (MSW) for
channel 0 and 6 (LSW) and 7 (MSW) for channel 1. You can reset this count by
setting the VR bit.

200

12.5K

500

5K

1 KHz

2.5K

2 KHz

1.25k

5 KHz

500

10 KHz

250

20 KHz

125

50 KHz

50

100 KHz

25

ATTENTION: Sample period times scaler must be less than 6.71 s in
order to avoid a zero frequency detect indication.

Relationship Between Sampled Pulses and Input Frequency

Input Frequency at Z
(Gate/Reset)
Terminal in Hz

Sampled Pulses for 1/2 Cycle of Z
(Gate/Reset) Pulse