40

Rockwell Automation Publication 1794-UM010D-EN-E - July 2013

Communicate With Your Module

Bit/Word Definitions

Output
Word

Bit

Definition

Word 0

00…15
(00…17)

Counter Control Word

00

Channel 0 Counter reset bit (CR) – A 0 to 1 transition of this bit
clears the counter. Outputs are adjusted according to the window
compare values.

01

Channel 0 Counter preset bit (CP) – A 0 to 1 transition of this bit sets
the counter to the value specified by the preset words. Outputs are
adjusted according to the window compare values.

02

Channel 0 Value reset bit (VR) – A 0 to 1 transition of this bit clears
the stored/accumulated count words.

03

This bit is always 0.

04

Channel 1 Counter reset bit (CR) – A 0 to 1 transition of this bit
clears the counter. Outputs are adjusted according to the window
compare values.

05

Channel 1 Counter preset bit (CP) – A 0 to 1 transition of this bit sets
the counter to the value specified by the preset words. Outputs are
adjusted according to the window compare values.

06

Channel 1 Value reset bit (VR) – A 0 to 1 transition of this bit clears
the stored/accumulated count words.

07

This bit is always 0.

08…10
(10…12)

Reserved for factory use.

11 (13)

Frequency/Resolution enhancement bit (M11) Set this bit to 1 for
frequency precision configuration (Refer to

Word 8 Bit/Word Definitions

on page

39

for details on frequency precision configuration).

Note: You must place a value between -4 and +2 in output word 2 and/
or 3 to shift the decimal position accordingly.

12…15
(14…17)

Reserved for factory use.

Word 1

00…15
(00…17)

Output Control Word

00

Output 0 Force output bit (FO) – When set to 1, output is turned on if
OE is 1. When FO = 0, output can be controlled by a compare match or
as directed by the PWM settings.

01

Output 0 Output enable bit (OE) – When set to 1, output can be
turned on from a force on, compare match or as directed by the PWM
settings. When OE = 0, the associated output is turned off.