Rockwell Automation Publication 1794-UM010D-EN-E - July 2013

Communicate With Your Module

Word 2

00…15
(00…17)

Channel 0 PWM Output value – When the module is configured for
PWM, the time base is enabled, the counter for the respective channel,
its gate interval, rollover and 1st on and 1st off value are used. Ties can
be used to direct the PWM signal to any or all outputs.
The range of the PWM values is 0

value

9500 decimal (for instance,

0.00%

value

95.00%). The actual duty cycle at the output depends

on the turn on and turn off times of the MOSFET, energy storage
capability of the cable/load and the resistance from output to return.

Word 3

00…15
(00…17)

Channel 1 PWM Output value – When the module is configured for
PWM, the time base is enabled, the counter for the respective channel,
its gate interval, rollover and 1st on and 1st off value are used. Ties can
be used to direct the PWM signal to any or all outputs.
The range of the PWM values is 0

value

9500 decimal (for instance,

0.00%

value

95.00%). The actual duty cycle at the output depends

on the turn on and turn off times of the MOSFET, energy storage
capability of the cable/load and the resistance from output to return.

Bit/Word Definitions

Configuration Word Definition

Configuration
Word

Bit

Definition

Configuration
Word 0

Counter Configuration – The upper byte of this word configures counter 1, the lower byte configures counter 0.

Bits 00…03

03

02

01

00

Counter 0

Bits 08…11
(10…13)

11
(13)

10
(12)

09
(11)

08
(10)

Counter 1

0

0

0

0

Counter

0

0

0

1

Encoder

0

0

1

0

Encoder X2

0

0

1

1

PWM

0

1

0

0

Encoder X4

0

1

0

1

Period/Rate

0

1

1

0

Continuous/Rate

0

1

1

1

Rate Measurement

Mode Selection

Bits 04…07

06

05

04

Counter 0

Bits 12…14
(14…16)

14
(16)

13
(15)

12
(14)

Counter 1

0

0

0

Store count disabled

0

0

1

Mode 1 – store/continue

0

1

0

Mode 2 – store/wait/resume

0

1

1

Mode 3 – store;reset/wait/start

1

0

0

Mdoe 4 – store;reset/start

Bit 15 (17)

Invert the Z signal – 0 = Z not inverted; 1 = Z inverted